Air-Cooled Modular Chiller, R32 CA-HANH Series

Характеристики
Cooling Capacity (kW): 
65-130
Heating Capacity (kW): 
71-142
Download brochureDownload brochure

Haier R32 series modular chillers are an innovative solution combining high energy efficiency with tomorrow's environmental standards. Intelligent control ensures a stable supply of cooling, heating and domestic hot water while maintaining acoustic comfort. The scalable structure makes them a universal choice for any project — from residential buildings to large commercial facilities.

Cooling capacity: 65–130 kW  |  Heating capacity: 71–142 kW

The Haier Super Clima B series delivers high-efficiency cooling, heating and domestic hot water production using the eco-friendly R32 refrigerant.

Haier R32 зовнішній вигляд
Haier R32 module

Maximum efficiency of the Haier R32 is guaranteed both at peak loads and during continuous year-round operation. These systems demonstrate exemplary performance, adapting to any operating mode throughout the entire season.

Efficiency chart

High-Efficiency Components

The DC inverter scroll compressor with EVI technology delivers high output power and system stability. It handles extreme cold weather with ease, providing efficient heating, and thanks to variable-speed control it regulates temperature precisely, significantly reducing energy consumption.


EVI Technology

Thanks to EVI technology, the heat pump operates reliably at outdoor temperatures below -30°C while significantly increasing heating capacity.

With integrated EVI technology, Haier heat pumps maintain stable operation and high performance even at critical outdoor temperatures down to -30°C. Vapour injection substantially improves the overall system COP, ensuring reliable heating in the harshest winter conditions.

EVI Technology

BPM Motors

BPM Permanent Magnet Motors

Optimised brushless permanent magnet (BPM) motors allow Haier to achieve peak efficiency while significantly reducing sound pressure levels. The brushless drive operates smoothly and energy-efficiently, delivering quiet operation in all load conditions.


Optimised Scroll & VCR Technology

Optimised Scroll and VCR for better adaptation to partial-load conditions and operational requirements, enhancing seasonal efficiency. The variable compression ratio (VCR) mechanism flexibly adjusts internal operating parameters, ensuring maximum performance and energy savings throughout the year. *VCR: Variable Compression Ratio

Scroll and VCR

Dual Compliance

Dual Compliance Sealing

The Dual Compliance design provides reliable compressor protection, preventing damage to the scroll assembly from foreign particles or liquid refrigerant. The optimised pressing force between the orbiting and fixed scrolls minimises internal friction and leakage, significantly extending the service life of the mechanism.


Swing Link Technology

The Swing Link technology in the compressor dynamically adjusts the interaction force between the orbiting and fixed scrolls as speed increases. This ensures stable operating parameters during speed changes, providing structural reliability and smooth operation when transitioning to high loads.

Swing Link

1000 mm DC Fan

The industry's largest axial fans increase airflow volume and improve heat exchange efficiency while reducing noise levels. Biomimetic blade design allows the fan to cut through air gently, ensuring stable performance and near-silent operation. Variable speed control via DC motors significantly improves seasonal efficiency.


U-Shaped Heat Exchanger

This one-piece heat exchanger increases the heat transfer area by 47% compared to previous models, allowing air to flow from all sides for maximum efficiency. Inner-grooved copper tubes create additional turbulence, while a hydrophilic coating on the aluminium fins improves moisture drainage and heat transfer. Optimal refrigerant distribution is achieved through two electronic expansion valves.


Shell-and-Tube Heat Exchanger

The patented design of this heat exchanger significantly improves system resistance to freezing and fouling. Internal baffles create the necessary flow turbulence, greatly enhancing heat transfer between the working media.


Wide Operating Range

The system is capable of stable operation across a wide range of working parameters. This makes it a universal solution that easily adapts to the most diverse facility requirements, ensuring reliable operation in various climatic conditions.

Operating range

Modularity & Cascading

Haier modular heat pumps offer maximum flexibility with automatic cascading requiring no third-party automation. By connecting up to 16 units in a single system, they easily scale to any load requirement, guaranteeing stable operation and simplified project design.

Haier modular system

5-inch touchscreen

Intuitive Control

The intuitive 5-inch touchscreen provides convenient control and monitoring of all system parameters. The interface offers quick access to advanced data for easy diagnostics during maintenance, while Modbus protocol support ensures seamless integration into building automation systems.


Technical Specifications

Model   CA0070HANH CA0100HANH CA0140HANH
Cooling
LWT 7°C / OAT 35°C
Capacity kW 65.0 100.0 130.0
Power input kW 22.03 28.60 42.88
EER W/W 2.95 3.50 3.03
Cooling
LWT 18°C / OAT 35°C
Capacity kW 73.0 110.0 145.0
Power input kW 18.96 23.40 40.28
EER W/W 3.85 4.70 3.60
Heating
LWT 35°C / OAT 7°C
Capacity kW 71.0 100.0 142.0
Power input kW 16.14 20.00 30.87
COP W/W 4.40 5.00 4.60
Heating
LWT 45°C / OAT 7°C
Capacity kW 71.0 100.0 142.0
Power input kW 18.93 24.20 36.90
COP W/W 3.75 4.13 3.85
Heating
LWT 55°C / OAT 7°C
Capacity kW 71.0 100.0 142.0
Power input kW 22.90 29.10 43.50
COP W/W 3.10 3.44 3.26
Seasonal
energy efficiency
SEER W/W 4.6 4.88 4.82
ηs,c % 181 192 190
SCOP (35°C) W/W 4.51 4.85 4.60
ηs,h (35°C) % 178 191 181
SCOP (55°C) W/W 3.65 3.85 3.80
ηs,h (55°C) % 143 151 149
Operating temperature
range
Cooling °C -20 ~ +53°C
Heating °C -30 ~ +50°C
DHW °C -30 ~ +50°C
Leaving water
temperature range
Cooling °C -5 ~ +20°C
Heating °C +20 ~ +60°C
Storage temperature range (tank) DHW °C 20 ~ 58°C
Power supply Ph/V/Hz 3N~/380~415 V/50 Hz
Sound power level dB 88 88 91
Sound pressure level dB(A) 71 70 72
Water-side heat exchanger type Shell-and-tube heat exchanger
Air-side heat exchanger type Copper with aluminium fins
Refrigerant expansion device Electronic expansion valve
Compressor Type DC inverter scroll compressor
Quantity 1 2 2
Refrigerant Type R32
Charge kg 10 11×2 11×2
CO₂e t 6.75 14.85 14.85
Fan Type Axial
Motor type DC motor
Airflow m³/h 25,400 20,500 25,400
Quantity 1 2 2
Water circuit Water pressure drop kPa 53 30 54
Water flow (cooling) m³/h 11.20 17.20 22.40
Water flow (heating) m³/h 12.20 17.20 24.40
Max. pressure MPa 1
Pipe size (inlet/outlet) DN50/DN50 DN65/DN65 DN65/DN65
Dimensions W×D×H mm 1260×1210×2260 2260×1255×2260 2260×1255×2260
Packing dimensions W×D×H mm 1280×1290×2400 2280×1275×2400 2280×1275×2400
Weight Net weight kg 500 910 910
Gross weight kg 515 940 940
Operating weight kg 525 973 973

1. Haier reserves the right to change these specifications without prior notice.
2. Rated specifications are calculated in accordance with EN14511 and EN14825.
3. Calculated in accordance with the Ecodesign Regulation for space cooling and heating products (813/2013, 2016/2281).
4. Ecodesign ratings are calculated at reduced water flow rate.
5. Noise data tested in Haier laboratory; actual values may vary depending on installation conditions.
6. Pressure drop values in the table do not account for the pressure drop across the built-in water filter.
7. CA0100HANH/CA0140HANH have two independent refrigerant circuits.

Dimensional Drawings

CA0070HANH

Dimensional drawing CA0070HANH

CA0100HANH / CA0140HANH

Dimensional drawing CA0100HANH CA0140HANH
Do you want to purchase?
Feedback form

Зворотний зв'язок